Find help with thermal imaging of switchboards for Melbourne properties.

Insurance thermography reports

What an insurer usually expects from a thermographic survey of switchboards, what the report should contain and how to brief a Melbourne provider.

An insurance thermography report is a written record of an infrared survey of a site’s switchboards and electrical plant, prepared so an underwriter or broker can see what was scanned, what was found and what is being fixed. Some commercial property insurers ask for one as a condition of cover or at renewal, so the deadline usually comes from the policy schedule rather than from a fault. Enquiries sent through this site go to independent thermography providers, who set their own scope, price and report template.

Illustrative photo for Insurance thermography reports

Why do insurers ask for a thermal survey?

Electrical faults inside switchboards can start fires that spread to stock, plant and neighbouring tenancies. A thermal survey gives the insurer evidence that the owner is finding overheating joints and overloaded circuits before they fail. One Melbourne provider’s insurance survey page says many insurers ask for a survey annually or every two years, depending on risk profile, claims history and the type of infrastructure. Your own policy wording is what counts, so read the schedule or ask your broker for the exact clause before you book anything.

Common triggers for the request include:

  • a renewal where the underwriter has added or changed a condition
  • a high-load site such as a cold store, plastics plant or commercial kitchen
  • an older main switchboard that has not been replaced in decades
  • a recent electrical incident or claim at the site
  • an expansion that has added plant to an existing board

What should the report contain?

A report an insurer can rely on usually includes:

Report section What it shows Why the insurer cares
Site and asset list Every board and item surveyed, with location Proves the survey covered the whole site, not a sample
Thermal and visual photo pairs Infrared image beside a normal photo of the same spot Lets an electrician find the fault later
Temperature difference and load How much hotter the fault was, and the current at the time A hot joint on a lightly loaded circuit is worse than it looks
Priority ranking Each fault graded from urgent to monitor Shows which items need action before renewal
Items not scanned Boards that could not be opened or reached, with the reason Stops gaps being mistaken for a clean result
Thermographer details Name, qualification and camera used Supports the weight given to the findings

Ask whether the thermographer is qualified to a recognised scheme. AS ISO 18436.7 sets out how people who carry out thermography for condition monitoring are qualified and assessed. Your broker may ask for the thermographer’s certification and level on the report.

How is this different from a general switchboard scan?

The camera work is the same. The difference is the paperwork and the follow-through. A maintenance scan for your own records can be brief. An insurance report has to stand up to someone outside the business reading it months later, and often has to be followed by proof that the urgent items were repaired. The switchboard thermal imaging scan guide explains the survey itself, including who should open the boards and why the site needs to be under load.

What the provider will need

  • the policy condition or broker email that describes the requirement
  • any report template the insurer supplies
  • the date the report must reach the broker
  • a list or plan of switchboards, motor control centres and other plant to include
  • who on site can give access to plant rooms, roof areas and locked tenancies
  • last year’s report, so repeat faults can be flagged

If the insurer wants proof of repair, say so at the start. The provider can then book a re-scan of fixed items and add a close-out section, which saves a second round of emails with the broker.

What the work involves on the day

The survey is done with the boards energised and carrying normal load, so it runs during working hours. Covers are removed by a licensed electrician or under their control, each section is imaged, and anything urgent is reported to the site contact before the provider leaves. The written report usually follows within an agreed time, and urgent items should not wait for it.

After the report, a licensed electrician carries out repairs. In Victoria, electrical installation work is certified with a Certificate of Electrical Safety, issued by a registered electrical contractor or licensed electrician. Keep the certificate with the report, because it is the record that the repair was done by a licensed person. The hot spot repair and re-scan page covers that step.

What it costs

Survey prices are quoted per site and rarely published. What you can budget for is the repair side: a 2026 Melbourne survey of electrician pricing puts a commercial call-out with the first hour included at $150 to $260. The thermal imaging cost guide for Melbourne lists the other published ranges and the things that move a survey quote.

What a careful provider will refuse to do

  • Issue a report for boards they did not open and scan
  • Mark a site clear when some boards were locked or unreachable
  • Downgrade an urgent fault because the renewal date is close
  • Backdate a report or reuse last year’s images

A thermographer may also decline to put their name to an insurer template that asks them to certify the whole electrical installation as compliant. A thermal survey shows heat; it is not a full inspection and test of the installation.

Local angle

Melbourne’s large manufacturing areas, such as the industrial estates around Campbellfield and Braeside, have many sites on commercial policies with plant running long shifts. Shopping centres, cold stores and strata buildings in the city also come up at renewal time. A survey booked six to eight weeks before renewal leaves time for repairs and a re-scan.

What to do next

Find the policy clause, the broker deadline and the board list. Then send an insurance thermography enquiry with the site address and renewal date so an independent provider can confirm whether they can meet it.

Send a job enquiry

Frequently asked questions

Which insurers ask for thermography?

It varies by insurer, industry and site risk, and conditions are set in each policy. The only reliable answer is your own policy schedule or a written note from your broker, so ask them for the exact wording before booking.

Can last year's report be reused for renewal?

No. A report records the condition on the day of the scan. Insurers asking for a current survey expect new images and readings. Last year's report is still useful for comparing repeat faults.

What if a board could not be opened during the survey?

The report should list it as not scanned and give the reason, such as locked access or a damaged cover. Arrange access and a short return visit, or tell your broker which items are still outstanding.

Do repairs have to be done before the report goes to the insurer?

That depends on the policy and the broker. Some want the survey report first and evidence of repairs later. Others want urgent items closed out before renewal. Ask the broker how they want urgent faults handled.

Who should hold the report?

The building owner or their manager should keep the report, the re-scan results and the electrician's certificates together. They form the maintenance record an insurer, auditor or future buyer may ask to see.