An electrical plant thermal survey extends a switchboard scan out to the equipment the boards feed: motors, pumps, fans, motor control centres, variable speed drives, compressors and the cables between them. The camera shows overheating terminals, bearings running hot, overloaded drives and blocked cooling before they stop production. The survey is carried out by independent providers who receive enquiries through this site, and each sets its own scope and price.

Illustrative photo for Electrical plant and motor thermal surveys

What does a plant survey look at?

Equipment What heat can show Typical cause
Motor control centre Hot starters, contactors and overload relays Worn contacts, loose terminations, undersized cable
Variable speed drive Hot heatsink or input terminals Blocked filters, failed fans, dusty enclosure
Electric motor body One end hotter than the other, or hot frame overall Bearing wear, misalignment, overload, poor ventilation
Motor terminal box Hot lug on one phase Loose or corroded connection
Belt and coupling Hot pulley or coupling face Slipping belt, misalignment
Cable trays and busways Warm sections along a run Overloaded circuit, bundled cables, damaged joints
Transformers on private sites Uneven heat on windings or bushings Overload or connection fault

Thermography for rotating plant is covered by AS ISO 18434.1, which introduces infrared thermography for condition monitoring and diagnostics of machines. It sets out general procedures rather than a fixed limit for every machine. The provider’s job is to compare like with like: the same motor last year, two identical pumps side by side, or three phases on one starter.

When is a plant survey worth doing?

  • Production lines where a motor failure stops the whole site
  • Cold stores and refrigeration plant, where a failed compressor costs stock
  • Buildings with large mechanical plant rooms, such as air handling units and chilled water pumps
  • Sites that already scan switchboards for insurance and want the plant included in the same visit
  • After a known overload, flood or dust event

On a smaller site, the switchboard scan may be enough. The switchboard thermal imaging page explains the board-only option.

Employer duties that sit behind it

WorkSafe Victoria says employers must provide and maintain systems of work that cover the provision, use, inspection, testing and maintenance of electrical equipment, so far as is reasonably practicable, and that maintenance and electrical work must be done by someone competent and suitably qualified. Those duties come from the Occupational Health and Safety Act 2004. A thermal survey is one way to show plant is being inspected; it does not replace the other checks your maintenance plan calls for.

What the provider will need from you

  • an equipment list or asset register, with motor sizes where known
  • a shift pattern, so the survey happens when plant is at working load
  • lockout and permit rules for the site, and who signs permits
  • guarding or access limits around moving plant
  • whether any drives or starters sit inside locked control panels
  • previous survey results, so trends can be read

Plant has to be running for the survey to mean anything. A provider will not ask you to stop a line; they will ask when each item runs at its usual load, and plan the route around that.

What the work involves

The thermographer walks the plant with the site’s maintenance lead. Control panels are opened by a licensed electrician or under their control, following the site’s procedures for work near live parts. Motors and couplings are imaged from a safe distance outside guarding. Readings are recorded with the load at the time, and the report ranks each item.

Mechanical findings such as hot bearings go to your fitter or maintenance contractor. Electrical findings go to a licensed electrician; the hot spot repair and re-scan page explains how that is handled and certified.

What it costs

Plant surveys are quoted per site and per item count, and providers do not publish standard rates. For the follow-up electrical work, a 2026 Melbourne price survey lists commercial electrician labour at $100 to $150 per hour and a fault finding visit at $160 to $420 per visit. More detail sits in the Melbourne switchboard thermal imaging cost guide.

What a careful provider will never skip

  • Asking for the site’s permit and isolation rules before arrival
  • Staying outside machine guarding while equipment is running
  • Recording ambient temperature and load with each reading
  • Flagging items that could not be surveyed because they were stopped or guarded
  • Separating mechanical and electrical findings so the right trade gets each job

They will also refuse to remove machine guards on running plant to get a better image. If an item cannot be seen safely, it goes on the report as not surveyed.

Local angle

Melbourne’s manufacturing is concentrated in the industrial council areas. Manufacturing is the largest employing industry in Hume and Kingston, according to economy.id, and in Greater Dandenong according to the council’s REMPLAN profile. Sites around Dandenong South and Derrimut range from older plants to newer logistics buildings, and both kinds carry motors and drives worth surveying.

What to do next

Pull together the asset list and shift times, then request a plant thermal survey with the site address, the main equipment and any production windows to avoid. An independent provider can then advise on scope and timing.

Send a job enquiry

Frequently asked questions

Can a thermal survey find bearing problems?

It can show a bearing housing running hotter than normal or hotter than an identical machine nearby, which points to wear, poor lubrication or misalignment. A fitter then confirms the cause, often with vibration analysis.

Does the plant need to run during the survey?

Yes. Motors, drives and starters only show faults under working load. The provider plans the route around production times so each item is imaged while it is doing its normal job.

Should switchboards and plant be done in one visit?

Usually it saves time and travel. The boards that feed the plant are scanned first, then the motors and drives, and one report covers the lot. Very large sites may split it over several visits.

Who fixes the faults a plant survey finds?

Electrical faults go to a licensed electrician. Mechanical faults such as hot bearings, belts or couplings go to your maintenance fitter or mechanical contractor. A good report separates the two.