Find help with thermal imaging of switchboards for Melbourne properties.

Hot spot repair and re-scan

What happens after a thermal scan finds hot spots: who can repair them in Victoria, the certificate to expect, repair costs and why a re-scan matters.

Hot spot repair is the electrical work that follows a thermal survey: remaking loose terminations, replacing damaged breakers, isolators or fuse carriers, cleaning and re-torquing busbar joints, and in the worst cases replacing the switchboard. A re-scan then images the repaired items under load to show the temperature has come down. Repairs requested through this site are quoted and done by independent licensed electricians, not by the site.

Illustrative photo for Hot spot repair and re-scan

Who can repair a hot spot in Victoria?

Repairs inside a switchboard are electrical installation work. Energy Safe Victoria says you must engage a registered electrical contractor, who will send a licensed electrician to do the work. Ask to see the licence card before work starts and check the contractor on the public register.

When the work is done, the registered contractor or licensed electrician completes a Certificate of Electrical Safety. Energy Safe Victoria’s consumer guidance on certificates says that for ordinary work a copy should reach you within 30 days. Work on consumer mains, the main switchboard, the meter box or the main earthing system is prescribed work: it must be inspected by an independent licensed electrical inspector, cannot be left turned on until inspected, and the copy should reach you within 4 days of the certificate being completed once inspection is done. These rules come from the Electricity Safety Act 1998 and the Electricity Safety (General) Regulations 2019.

Typical repairs by finding

Finding in the report Usual repair Re-scan needed
Loose cable termination on a breaker Isolate, clean, remake and torque the connection Yes
Hot breaker body with good terminations Replace the breaker with a matched rating Yes
Hot busbar joint Isolate the board, clean and re-torque the joint Yes
One phase much hotter than the others Rebalance circuits across phases, check for overload Yes
Overheated rewireable fuse carrier Replace with circuit breakers and safety switches Yes
Heat damage spread across the board Switchboard replacement, with inspection Yes
Hot item on a motor or drive Electrical or mechanical repair depending on cause Yes

Why does the board need to be switched off?

A loose connection cannot be fixed safely while it is live. Most repairs need the circuit or the whole board isolated, which means planned downtime. For a factory, a shopping centre or an apartment block, the provider will ask when an outage can happen, who needs notice, and whether a generator is needed for essential loads. In strata buildings, the owners corporation manager usually sends the notice. Consumer Affairs Victoria says the Owners Corporations Act 2006 requires an owners corporation to repair and maintain common property, fixtures and services, so the manager typically approves and pays for repairs to common boards.

What a re-scan proves

A re-scan images the same items from the same angles, with similar load, after repair. If the temperature difference has dropped to normal, the fault is closed and the report can say so. If it has not, the cause may be overload rather than a loose joint, and the electrician needs to look at circuit loading or cable size. Insurers that ask for a thermography report often want this close-out evidence.

The re-scan is only as good as the load at the time. Booking it for the same time of day and week as the first survey gives the fairest comparison.

What it costs

Repair costs come from published electrician rates in Melbourne. A 2026 price survey lists:

  • commercial electrician labour at $100 to $150 per hour
  • a fault finding or diagnostic visit at $160 to $420 per visit
  • a safety switch added or replaced on an existing board at $160 to $370 per switch
  • a single-phase switchboard upgrade at $945 to $2,950
  • a commercial three-phase switchboard upgrade at $2,100 to $6,200

Parts, after-hours work for planned outages, and inspection fees for prescribed work add to these. The Melbourne cost guide explains how to compare repair quotes against the survey findings.

What a careful electrician will refuse to do

  • Tighten connections on a live board to save an outage
  • Replace a breaker with a higher rated one to stop it tripping or running hot
  • Clear a hot spot without finding why it formed
  • Energise prescribed work before the licensed electrical inspector has inspected it
  • Skip the Certificate of Electrical Safety on a small job

Upsizing a breaker to stop heat or nuisance trips can leave a cable unprotected. A careful electrician will find the overload instead.

Local angle

Older Melbourne buildings, from inner-city commercial blocks to post-war factories in the south-east, can still have switchboards with ceramic fuses or tightly packed additions. Repairs there can turn into a board replacement once the cover is off. In newer industrial buildings in places like Derrimut, repairs are more often about heavy plant loads on one phase. If the survey has not yet been done, start with the switchboard thermal imaging guide.

What to do next

Have the thermal report ready, with the priority list and photos. Then ask for hot spot repair quotes and include the outage windows that suit your site, so an independent electrician can plan isolation and the re-scan together.

Send a job enquiry

Frequently asked questions

How urgent is a hot spot?

That depends on how much hotter it is than the reference point, the load at the time and what it feeds. The report should rank each fault. Anything marked urgent needs a licensed electrician to look at it as soon as possible, not at the next annual scan.

Can the repair be done without an outage?

Rarely. Remaking connections and replacing breakers needs the circuit or board isolated. The electrician will plan the shortest practical outage and tell you what loses power.

Do I need a certificate for a small repair?

Electrical installation work in Victoria is certified with a Certificate of Electrical Safety from the registered contractor or licensed electrician. Ask for it on every repair job, including small ones.

When should the re-scan be done?

After all the repairs are complete and the site is back at normal load, ideally at a similar time of day and week to the first scan, so the readings can be compared fairly.

What if the re-scan still shows heat?

Then the joint was probably not the whole story. The circuit may be overloaded, the cable undersized, or the phases unbalanced. The electrician needs to measure the load and find the cause.